ZigBee remote control thermostat with relay output
 |
This is a radio battery powered thermostat that can be connected to a PC-SCADA or a PLC through ZigBee and one of the Gateway that belong to the 4-noks products family. It is equipped with a wide LCD display and 4 buttons in order to have a simple user interface.
|
 |
It is also equipped with a bi-stable relay and so it may replace an ordinary thermostat giving a remotely controlled system. This thermostat has two different operating modes to activate output: heating/cooling mode or heating set temperature mode (Auto/Comfort/Background/Frost protection). This device periodically makes available the values of room temperature, current temperature and the operating mode currently active. All functions are remotely controllable.
Key features
|
- Full remotely configurable thermostat
- Wide 3 digit display
- 4 buttons
- Bi-stable relay output to achieve low power consumption
- Battery powered
- Internal antenna
|
Technical Specs
| General characteristics |
Chip Ember EM250 Compatible IEEE 802.15.4 Stack EmberZnet 3.5.x (ZigBee PRO) Modbus/RTU Wall mounting with screws |
| RF characteristics |
Frequency: 2405 MHz ÷ 2480 MHz Modulation: DSSS Nominal transmission power: 2mW (3 dBm) Reception sensitivity: -95 dBm Internal antenna gain: 0 dB Coverage outdoor/indoor: 100m/30m |
| Power supply |
3 AAA Batteries 1,5V Battery life: 2 years in case of one transmission every 5 minutes at 20°C |
| Thermostat |
Auto/Comfort/Background/Frost protection operating mode (remotely configurable) Heating/Cooling operating mode (remotely configurable) Hysteresis: -/+1°C (remotely configurable) Set temperature range +8/+32°C (remotely configurable) Temperature resolution: 0,1°C Temperature accuracy: ±1°C |
| Relay |
Bistable with 250V/5A rated contacts |
| Environment parameters |
Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing Degree of protection: IP 30 |
| Approvals |
ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions ETSI EN 301 489: Radio Compatibility EN 61000-6-2: Electromagnetic Compatibility - Emissions EN 61000-6-3: Electromagnetic Compatibility - Immunity EN 60950-1: Electric Safety |
|