ZR-TIDCI

ZigBee S0 pulse counter with router

ZR-TIDCI

The ZR-TIDCI-EM is a permanent powered ZigBee device, capable to count pulses emitted from flow rate meters (water, gas, electricity,...) and to measure the temperature from both the 2 on board NTC inputs.

modbus-logo ha-logo

Pulse counters and temperature samples are sent at regular intervals to a gateway of 4-noks products family. Moreover, if temperature sensors are installed into an hydraulic circuit in the inlet and outlet pipes this device can send the difference between them.

ZR-TIDCI
Enlarge
ZR-TIDCI
Enlarge
ZR-TIDCI
Enlarge
Flyer
User manual

 

Key features

  • 2 pulse counter inputs S0 compatible
  • 2 thermal resistor inputs (NTC resistors not included)
  • Sampling and transmission rates are configurable
  • 12-24 Vdc/Vac supply
  • Routing function
  • External antenna
  • RF power amplifier: 10 mW

Technical Specs

General characteristics
Chip Ember EM250
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Modbus/RTU
Device address settable via internal dip-switch
Wall mounting with screws
Cable gland: PG9
RF characteristics Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 10mW (10 dBm)
Reception sensitivity: -97 dBm
External antenna gain: 5,5 dB
Coverage outdoor/indoor: 200m/50m
Supply 12-24 Vdc/Vac; 100mA; 50/60Hz
Thermal sensor input NTC type resistor
103AT type (R25 = 10 KOhm; Beta = 3435K)
Measurement range: -50°C ÷ +110°C
Measurement resolution: 0,1°C
Measurement accuracy : ±0,5°C
Measures are linearized at tenth of degree
Digital inputs Electronic type not insulated inputs for clean contact
Short circuit current 0,01mA. Use self-cleaning contact
Connections Pull out terminals (3,81 mm pitch)
Environment parameters Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
Degree of protection: IP 55
Approvals ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions
ETSI EN 301 489: Radio Compatibility
EN 61000-6-2: Electromagnetic Compatibility - Emissions
EN 61000-6-3: Electromagnetic Compatibility - Immunity
EN 60950-1: Electric Safety